TECHNICAL SPECIFICATIONS FOR MACLINE SERIES ONLINE UPS
The MACLINE Series is the powerful single phase ONLINE family of uninterruptible power supplies by MAC POWER SYSTEMS. The MACLINE Series provides reliable protection for all high-end applications and is extensively equipped to master all event qualities. All this has helped us to become the leading online UPS Company in India. MACLINE series covers 1 KVA to 10 KVA (Single Phase) Online UPS.

PARAMETERS

TECHNICAL SPECIFICATIONS

Capacity 1 KVA/800W, 2 KVA/1600W, 3 KVA/2400W, 5 KVA/4000W, 7.5 KVA/6000W, 10 KVA/8000W (Max.)
Configuration/Technology Standalone Tower Configuration, On-line double conversion with IGBT technology or equivalent & pure Sine wave PWM; Generator compatible; having inbuilt isolation transformer; Battery charging current selector; Inbuilt over voltage cut off device.
Input Phase Single Phase
Normal Voltage 220V ± 15%
Range of Voltage Variation at Full Load ≤ 170 VAC to ≥270 VAC
Source Mains/D.G set
Frequency 50 Hz ± 5Hz(Suitable for Generators)
Power Factor 0.8
Electrical Connection As per Capacity of the UPS
Output Voltage 230 VAC ± 1 %
Voltage Regulation ± 1%
Frequency 50 Hz ±0.05Hz
Voltage Distortion ≤ ± 3%
Wave Form Pure Sine wave
Transient Response <8(10% ~90% Linear Load)%
Voltage Harmonic ≤3 (Linear Load)%
Overload Capacity 110% Continuous; 111 to 150% : 18 Sec; ≥150% : 5 Sec
Power Factor 0.85
Electrical Connection As per Capacity of the UPS
Crest Factor 4 :1
LED Display Mains On, Charger On, UPS on Battery, Battery Low, Output On, Overload, Reset
LCD Display Input & Output Voltage, Frequency & Current # DC Voltage #
Charging & Discharging Current, Battery Low
Environmental

  1. Operating Temperature
  2. Storage Temperature
  3. Humidity
  4. Audible Noise level
 

0-45º C (Continues)
0-60º C
10-90%(Non Condensing)
<55 dB at full load unto distance of 1 mtr.

Interface Db9 Optional (As per requirement)
Static By Pass Optional (As per requirement)
Manual Bypass switch Optional (As per requirement)
Efficiency (AC-AC) ≥85** (Full Load)%
Built in Isolation Transformer 1 KVA to 10 KVA,  with Isolation Transformer
SMF external Battery Backup As per customer requirement
Rack Iron Made with Silver paint
Recharge time 4-5 hours for 90% of full capacity
Emergency trip Yes
Equipment cooling Suitable capacity fans for air circulation in the UPS systems battery cabinet and in UPS machine
Protection factor Against surges and spikes, low and high frequency cut-off, input under and over voltage trip, battery low voltage, output over voltage, excess battery charging protection through mains cut-off, overload/ short circuit electronic shutdown, fast acting semi conductor fuses for thyristor, HRC fuses for inverter output/input, current limiting features, HRC fuses for D.C. Filter capacitors, HRC fuses for control circuits, Galvanic isolation between input and output
  • Due to Continuous R & D, Specifications are subject to change.
  • Customerised specifications are also available.
  • Hot standby and Parallel Redundant UPS is also available on request.